What Are the Faults in a Power System
Power system faults are generally divided into two major categories: shunt faults and series faults.
Shunt faults refer to various types of short‑circuits, including three‑phase short‑circuit, two‑phase short‑circuit, single‑phase‑to‑ground short‑circuit and two‑phase‑to‑ground short‑circuit.
During a three‑phase short‑circuit, the impedances of the three short‑circuited phases are equal. As a result, three‑phase currents and voltages remain balanced, hence it is also known as a symmetrical short‑circuit.
For the other types of short‑circuits, the three‑phase symmetrical configuration of the system is destroyed, and three‑phase voltages and currents in the network are no longer balanced. These are therefore called unsymmetrical short‑circuits.
Operational experience shows that single‑phase short‑circuits account for the majority among all power‑system short‑circuit faults. Although three‑phase short‑circuits occur infrequently, their consequences can be severe and deserve sufficient attention. Furthermore, three‑phase symmetrical short‑circuit calculation serves as the basis for unsymmetrical short‑circuit calculation.
Series faults mainly denote various open‑conductor faults, including single‑phase open‑circuit, two‑phase open‑circuit and three‑phase open‑circuit.
Symmetrical‑Component Transformation for Power‑System Relay Protection
In a three‑phase circuit, any set of unbalanced three‑phase phasors can be decomposed into three sets of balanced three‑phase components. This is the so‑called symmetrical‑component method for three‑phase phasors. The symmetrical‑component method decomposes unbalanced three‑phase currents and voltages into three groups of symmetrical components, namely:
(1) Positive‑sequence components: The three positive‑sequence components have equal magnitudes, with phase angles differing by \(2\pi/3\) from one another. Their phase sequence is identical to that of the system under normal operating conditions.
(2) Negative‑sequence components: The three negative‑sequence components have equal magnitudes, with phase angles differing by \(2\pi/3\) from one another. Their phase sequence is opposite to that of positive‑sequence components.
(3) Zero‑sequence components: The three zero‑sequence components have equal magnitudes and identical phase angles. For clarity, subscripts a, b and c are conventionally used to denote the three phase components.